Question
I have couple questions about F617R2-R72+.
1. How do the power modules do the redundancy? Is it true that if one fails the other 3 will share the loading?
2. Will the nodes also do redundancy? I don’t think so but customer wants conformation.
Print
Answer
RHS PSU and LHS PSUs are totally separated so if one PSU failed the other PSU on the same side can take over 100% loads.

The nodes by themselves are not redundant. However, by checking heartbeat from other nodes via LAN ports, these Fat Twin nodes can be fail-over.
Was this FAQ helpful?